-11%
The NW-8300-32 Conventional Fire Control Panel is engineered for effective fire detection and alarm systems, suitable for various environments. It operates on a mains voltage of 110-240 AC (±10%) at 50Hz, ensuring compatibility with diverse power systems. The unit is equipped with two 12V 7Ah batteries, providing reliable backup power. This control panel maintains a nominal system voltage of 29V DC, with a maximum voltage ripple of 200mV, ensuring stable performance. Each zone functions at a nominal voltage of 21V DC (within a range of 20-22.5V) and supports a maximum of 20 devices per zone. Adjustable sounder activation delays range from 0 to 18 minutes, with increments of 30 seconds for customizable responses. The panel incorporates 4.7kΩ resistors for both zone and sounder end-of-line devices, maintaining circuit integrity. Additionally, it features short circuit protection for zones set at 100mA, enhancing safety and reliability.
Feature | Specification |
---|---|
Model | NW-8300-32 |
Mains Voltage | 110-240 AC ± 10%, 50Hz |
Battery Voltage | 2 x 12V / 7Ah |
System Voltage | 29V DC Nominal |
System Voltage Ripple | 200mV MAX |
Charger Size | Up to 7Ah in 24 hours |
Zone Voltage | 21V DC Nominal (20-22.5V) |
Maximum Zone Capacity | 20 devices per zone |
Sounder Activation Delay | 0-18 Minutes (30s increments) |
Zone End of Line Device | 4.7kΩ Resistor |
Sounder End of Line Device | 4.7kΩ Resistor |
Zone Short Circuit Protection | 100mA |