The Sporlan Type ADR discharge bypass regulating valves, featuring a durable brass body, are available in both direct-acting and pilot-operated configurations. Designed to limit the minimum evaporating pressure during low-load periods, these valves prevent coil icing or compressor operation below the designed suction pressure. They undergo rigorous factory testing to ensure leak-free performance. The valves offer adjustable settings, with direct-acting valves available in both adjustable and nonadjustable options, while pilot-operated valves feature adjustable settings and include a solenoid stop feature for added control and reliability. Additionally, an optional inlet strainer is available for enhanced protection.
Feature | Specification |
---|---|
Type | Piston |
Operation | Electric |
Function | Pressure-control |
Body | Brass, copper |
Applications | Industrial, refrigeration, air conditioning |
Associated function | Discharge |
Other characteristics | Bypass |
DN (Diameter Nominal) | Min.: 0.25 in, Max.: 1.125 in |
Pressure | Min.: 0 bar (0 psi), Max.: 6.9 bar (100.1 psi) |